Enter one-way length
Enter the distance from supply to load once. The single-phase factor already accounts for the outgoing and return paths. Doubling the input length doubles that allowance again.
Use the right impedance units
Imperial mode expects resistance and reactance in ohms per 1,000 feet. Metric mode uses ohms per kilometre. Switching units converts both the length and impedance while preserving the physical calculation.
Know the model
The calculation projects resistance and reactance onto a lagging power-factor angle. Three-phase mode assumes a balanced load. It is an estimate and does not solve unbalanced circuits, harmonics or conductor temperature.
Check an independent example
At 120 V, 20 A, a 100-foot one-way run and 2 ohms per 1,000 feet, a resistive single-phase circuit drops 8 V, or 6.67%. A starting-current multiplier scales that estimated drop using the same circuit impedance.