Conduit Math
Menu

Voltage drop calculator

Estimate single- or three-phase drop with resistance and reactance.

Measurements

Voltage drop3.22%
Voltage drop
7.72 V
Load voltage
232.28 V
Starting drop
7.72 V
Starting drop
3.22%

Calculated estimate

How it is calculated

ΔV = K × I × L × (R × PF + X × √(1 − PF²)) ÷ 1000
K = 2 single phase; √3 three phase

Before you use the result

One-way length; balanced load and lagging power factor. Use conductor impedance at the intended operating temperature. Starting drop scales current only.