Voltage drop calculator
Estimate single- or three-phase drop with resistance and reactance.
Voltage drop3.22%
- Voltage drop
- 7.72 V
- Load voltage
- 232.28 V
- Starting drop
- 7.72 V
- Starting drop
- 3.22%
Calculated estimate
How it is calculated
ΔV = K × I × L × (R × PF + X × √(1 − PF²)) ÷ 1000 K = 2 single phase; √3 three phase
Before you use the result
One-way length; balanced load and lagging power factor. Use conductor impedance at the intended operating temperature. Starting drop scales current only.