Read primary and secondary line currents for a 50 kVA transformer in single-phase and balanced three-phase examples.

Read the nameplate for each side

Enter the apparent power rating in kVA and each winding side’s rated voltage. For a balanced three-phase transformer, use total three-phase kVA and line-to-line voltage on each side. A 480 V to 240 V transformer has twice as much secondary current as primary current at the same apparent power.

Compare single-phase and three-phase current

In single phase, 50 kVA at 480 V gives 50,000 ÷ 480 ≈ 104.17 A on the primary and 208.33 A at 240 V on the secondary. In balanced three phase, divide by √3 as well. The corresponding line currents are about 60.14 A and 120.28 A.

Use the result as a full-load estimate

The result represents rated apparent power at the entered voltages. Actual current depends on the connected load. Starting inrush, transformer losses, conductor ampacity and protective-device selection each require a separate check.