Start with the rise
Measure the perpendicular distance between the two conduit centerlines. Enter that height and the angle of each bend. The two bends have equal magnitude and opposite direction.
Geometry follows the triangle
Ideal spacing is height divided by sine of the angle. Shrink is height multiplied by tangent of half the angle. A 6-inch rise at 30° gives 12 inches between marks and about 1.608 inches of shrink. The displayed shrink rounds to 1 5/8 inches.
The chart is a different method
Klein’s 30° chart uses a multiplier of 2 and shrink of 1/4 inch per inch of offset. The same 6-inch rise therefore gives 12 inches between marks and 1 1/2 inches of shrink. Keep spacing and shrink from the same selected method.
Check the finished bend
The sketch is not to scale. Conduit size, shoe radius and springback affect the finished shape. Make a trial bend when changing benders or material, and check the actual clearance.
Source · Klein Tools, Conduit Bender Guide, “Offset Formula Table,” p. 6.