Wire size calculator for voltage drop
Compare conductor areas against a resistance-only drop target.
Minimum area for target10 AWG
- Voltage drop
- 4.86 V
- Voltage drop
- 2.02%
- Load voltage
- 235.14 V
- Resistance
- 1.2138 Ω/1000 ft
- Maximum resistance
- 1.8 Ω/1000 ft
Calculated estimate
How it is calculated
R(candidate) = R(reference) × area(reference) ÷ area(candidate)
Before you use the result
Resistance-only, unity power factor, same material and temperature. This is not an ampacity or code-compliance check.