Conduit Math
Menu

Wire size calculator for voltage drop

Compare conductor areas against a resistance-only drop target.

Measurements

Minimum area for target10 AWG
Voltage drop
4.86 V
Voltage drop
2.02%
Load voltage
235.14 V
Resistance
1.2138 Ω/1000 ft
Maximum resistance
1.8 Ω/1000 ft

Calculated estimate

How it is calculated

R(candidate) = R(reference) × area(reference) ÷ area(candidate)

Before you use the result

Resistance-only, unity power factor, same material and temperature. This is not an ampacity or code-compliance check.